Refrigerant R-410A
Residential and Commercial Air Conditioning Gas
R-410A is a near-azeotropic HFC blend of R-125 and R-32. R-410A is a non ozone depleting product for commercial and residential air conditioning systems as an alternative to R-22. R-410A exhibits higher pressure than R-22 so it is used in new equipment rather than as a retrofit gas.
APPLICATIONS:
- Residential and Commercial Air Conditioning: Small Air Conditioners and for Domestic and Commercial Heat Pumps, VRV & VRF.
- Industrial Air Conditioners: Air Conditioning for the Processing Industry.
USAGE INSTRUCTIONS:
- R-410A refrigerant operates at 50%-70% higher pressure than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A.
- R-410A systems should be charged with liquid refrigerant.
SPECIFICATIONS:
Inspection Time | Unit | Value |
Appearance | – | Clear, Transparent and Colorless |
Purity | % (m/m) | ≥ 99.5 |
Water Content | % (m/m) | ≤0.0010 |
Evaporation Residue | % (m/m) | ≤0.010 |
Acid Content (as HCI) | % (m/m) | ≤0.0001 |
Non Condensable Gas | % (m/m) | ≤1.5 |
DewGas R-410A Refrigerant adheres to quality as per AHRI-700 standard:
ISO Tank | : | 19000 kgs |
Toner | : | 740 kgs net weight |
Big Cylinder | : | 45 kgs net weight |
Small Cylinder | : | 8 kgs & 10 kgs net weight |
Composition | R- 125 (50%) R-32(50%) |
Chemical Name | Pentafluoroethane, Difluoromethane |
Class | HFC / Near azeotropic Blend |
ASHRAE Safety Classification | A1 non – toxic and non – flammable |
GWP* | 2088 |
Recommended Lubricant | POE |
Crit. Temperature | 71.34°C |
Crit. Pressure | 49.01 Bar |
Boiling Point at 0 Bars (g) | -49.01 Bar |
Inspection Time | Unit | Value |
Appearance | – | Clear, Transparent and Colorless |
Purity | % (m/m) | ≥ 99.8 |
Water Content | % (m/m) | ≤0.0010 |
Evaporation Residue | % (m/m) | ≤0.010 |
Acid Content (as HCI) | % (m/m) | ≤0.0001 |
Non Condensable Gas | % (m/m) | ≤1.5 |